EasyManuals Logo
Home>Daikin>Inverter>LX10F11B3

Daikin LX10F11B3 User Manual

Daikin LX10F11B3
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
Symptom Cause Checkpoint Remedy
Control is unstable (during chilled in range control operation).
The control
temperature is
unstable.
Faulty low
pressure
transducer LPT
Replace the LPT.
Correct
installation
of DCHS
Improper installation
of EOS, EIS
and SGS?
Is the difference
in pressure between the pressure
gauge and LPT 30 kPa
or more?
Is the DCHS 1, 2
or heat insulation installed
improperly ?
Installation check of RS and SS
Repair
Installation
of EOS,EIS
and SGS
YES
YES
YES
NO
NO
NO
Operating temperature
is fluctuating.
Faulty discharge
pipe temperature
sensor DCHS 1, 2
Pipe temperature
sensor fault
EOS,EIS,SGS
Air temperature
sensor fault RS,SS
Temperature
continues to
decrease.
Stop of evaporator
fan
Condenser fan stop
Check the fan
motor.
Temperature continues
to decrease.
Check the SS and RS.
YES
NO
Temperature
continues to
increase.
Solenoid valve
HSV or RSV
internal leak
Excessive frost on
the evaporator
YES
Is outlet side
pipe of HSV or
DSV hot?
Check operation of the
HSV, RSV.
Replace the HSV,
RSV.
NO
Temperature continues
to increase.
Manual defrost
2-51
02章45-54LX10F11B3TR16-02En.indd2-5102章45-54LX10F11B3TR16-02En.indd2-51 2016/02/029:37:432016/02/029:37:43
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals