3-9
No. Inspection item Inspection content 2nd year 4th year 8th year
Electrical system
1
Damage of power cable
and plug
✓✓✓
2
Inspection of condition of
internal wiring
✓✓✓
3
Terminal looseness
inspection and retighten if
necessary
1) Magnetic switch ✓✓✓
2) Electronic connection ✓✓✓
4
Condition of monitoring
receptacle cover
✓✓✓
5 Condition of PC port cover ✓✓✓
6 Fuse conditions Open or short connection ✓✓✓
7
Magnetic switch contact
point inspection and
replacement
1) Contact point inspection ✓✓✓
2) Replace the contact on
evaporator fan motor
3) Replace the contact on
condenser fan motor
8 Electric insulation check
1) Power cable and plug ✓✓✓
2) Compressor ✓✓✓
3) Evaporator fan motor ✓✓✓
4) Condenser fan motor ✓✓✓
9 Temperature sensor
1) Installation condition of sensors ✓✓✓
2) Inspection of sensor and sensor
cable for damage
✓✓✓
3) Alarm indication ✓✓✓
10 Humidity sensor Inspect every year. ✓✓✓
11
PT/CT (voltage and
current) Alarm indication
✓✓✓
12
Pressure sensor Alarm
indication
✓✓✓
13 Condenser fan motor Inspection of bearing ✓✓
14 Evaporator fan
Deformation and damage inspection
✓✓✓
15 Condenser fan
Deformation and damage inspection
✓✓✓
03章LX10F11B3TR16-02En.indd3-903章LX10F11B3TR16-02En.indd3-9 2015/12/2115:43:112015/12/2115:43:11