EasyManuals Logo

Daikin MicroTech II User Manual

Daikin MicroTech II
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
www.DaikinApplied.com 11 OM 752-4
GettInG started
Figure 5: Changing a keypad/display menu item
Table 7: Keypad/display menu item list
Display
Keypad menu
item list
Abr. Description
RO
RW
1
06 Default
ra
Reset Alarm Input Enter 1 to clear alarms (clears all inactive alarms, except lter alarm). To enable the alarm again, enter 0. RW x
2
hc
UVC (Heat/Cool)
Mode Output
UVCM Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg. Heat, 9 = Fan Only RO x
st
UVC State Output UVCS
Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 = Heat, 6 = ActiveDe-
hum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11 = Heat Mode Cant Heat, 12 = CantCool,
13 = Emerg Heat Mode Cant Heat, 14 = Heat Mode Low Limit, 15 = Cool Mode Low Limit
RO x
d0
Discharge Air Temp
Set point Output
DATS Display current DA temperature set point. RO x
d1
Discharge Air Temp
Output
DAT Display current DA temperature. RO x
d2
Ventilation Cooling
Low Limit set point
VCLL Adjust economizer cooling DA temperature low limit. RW x
54°F
(12°C)
d3
Mechanical Cooling
Low Limit set point
MCLL Adjust mechanical cooling DA temperature low limit. RW x
45°F
(7°C)
sl
Slave Type
Conguration
Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave follows master). This
feature requires a network over which the master and slave UVCs can communicate.
RW x 0
e0
Effective Occupancy
Output
Display current occupancy. RO x
xc
Occupancy Override
Input
Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting this variable is
intended only for troubleshooting. Once you are done, cycle unit power to clear this variable and return
the UVC to normal operation.
RW x
2
cx
Occupied Cooling set
point
OCS Adjust occupied cooling set point. RW x
73.4°F
(23°C)
cs
Standby Cooling Set
point
SCS Adjust standby cooling set point. RW x
77°F
(25°C)
cu
Unoccupied Cooling
Set point
UCS Adjust unoccupied cooling set point. RW x
82.4°F
(28°C)
hx
Occupied Heating Set
point
OHS Adjust occupied heating set point. RW x
69.8°F
(21°C)
hs
Standby Heating Set
point
SHS Adjust standby heating set point. RW x
66.2°F
(19°C)
hu
Unoccupied Heating
Set point
UHS Adjust unoccupied heating set point. RW x
60.8°F
(16°C)
rs
Wall Sensor Type Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F. RW x 0
x1
Outside Air Damper
Position Output
OADP Display OA damper position. RO x
x2
OAD Min Position
High-Speed Set point
OADH
Adjust OA damper minimum position with IAF at high speed. (This variable is factory set to 5% open
when the unit is ordered with optional CO
2
DCV.)
RW x 20%
x3
OAD Min Position
Med-Speed Set point
OADM
Adjust OA damper minimum position with IAF at medium speed. (This variable is not used when the op-
tional CO
2
DCV is enabled. Only OADH is active as the OA damper minimum regardless of fan speed.)
RW x 25%
x4
OAD Min Position
Low-Speed Set point
OADL
Adjust OA damper minimum position with IAF at low speed. (This variable is not used when the optional
CO
2
DCV is enabled. Only OADH is active as the OA damper minimum regardless of fan speed.)
RW x 30%

Table of Contents

Other manuals for Daikin MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech II and is the answer not in the manual?

Daikin MicroTech II Specifications

General IconGeneral
BrandDaikin
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals