IM 972-2 • MAVERICK I ROOFTOP SYSTEMS 46 www.DaikinApplied.com

Figure 39: System Charging Chart: MPS 025B
25 TON, CIRCUITS 1 & 2
55
65
75
85
95
105
115
225
250
275
300
325
350
375
400
425
450
475
500
525
550
575
100 105 110 115 120 125 130 135 140 145 150
155
160 165
225
250
275
300
325
350
375
400
425
450
475
500
525
550
575
100 105 110 115 120 125 130 135 140 145 150
155
160 165
55
65
75
85
95
105
115
25 TON, CIRCUIT 1
25 TON, CIRCUIT 2
BOTH COMPRESSORS MUST BE OPERA
TING BEFORE CHECKING
REFRIGERANT CHARGE.
BEFORE FINAL REFRIGERANT CHECK!
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT
CONDITIONS
MEASURE PRESSURE AT C
OMPRESSOR SUCTION AND DISCHARGE.
MEASURE OUTDOOR AMBIENT TO UNIT.
PLACE (X) ON CHART
WHERE SUCTION AND DISCHARGE INTERSECT.
IF (X) IS BELOW OUTDOOR AMBIENT LINE,
ADD CHARGE AND REPEAT
STEPS 1-3.
IF (X) IS ABOVE OUTDOOR AMBIENT LINE, RECOVER EX
CESS CHARGE
AND REPEAT STEPS 1-3.
CAUTION:
INSTRUCTIONS:
DISCHARGE PRESSURE (PSIG)
OUTDOOR AMBIENT ( F, DB)
SUCTION PRESSURE (PSIG)
DISCHARGE PRESSURE (PSIG)
OUTDOOR AMBIENT ( F, DB)
SUCTION PRESSURE (PSIG)
SYSTEM CHARGE CHART - REFRIGERANT 410A