Installation manual
20
REYQ8~16P8Y1B
VRVIII System air conditioner
4PW39996-1B
4 The weighed and already recorded amount of additional
refrigerant charge (not the total amount of refrigerant present in
the system) must be entered by selecting the corresponding
LED display.
Scroll through the possible LED combinations by pressing the
button until the LED combination corresponds to the
weight of additional refrigerant charge you must input.
Select the required input by pressing the button
and confirm the input into the PCB by pressing the
button again.
Possible LED combinations in function of weight of additional
refrigerant charge (= x) to input;
5 Return to setting mode 1 (= initial state) by pressing the
button.
Perform a test operation as described in "12.4. Test operation" on
page 23.
11.7. Checks after adding refrigerant
Are the stop valves for both liquid and gas open?
Is the amount of refrigerant, that has been added, recorded on
the refrigerant charge label?
12. BEFORE OPERATION
12.1. Service precautions
Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Be sure to turn off the main switch and to remove the
fuses from the control circuit located in the outdoor unit.
kg
H1P H2P H3P H4P H5P H6P H7P
0 x=0
w xxxxxx
1 0<x<5
w xxxxxw
25x<10
wx x x xwx
310x<15
w xxxxww
415x<20
wx x xwx x
520x<25
wx x xwxw
625x<30
w xxxwwx
730x<35
w xxxwww
835x<40
wx xwx x x
940x<45
wx xwx xw
10 45x<50
wx xwxwx
11 50x<55
wx xwxww
12 55x<60
wx xwwx x
13 60x<65
wx xwwxw
14 65x<70
wx xwwwx
15 70x<75
wx xwwww
16 75x<80
wxwxxxx
17 80x<85
wxwx x xw
18 85x<90
wxwx xwx
19 90x<95
wxwx xww
20 95x<100
wxwxwx x
21 100x
wxwxwxw
NOTE
If you get confused in the middle of the input
process, press the button to return to
setting mode 1 (= initial state).
The H1P LED is off
x.
Resume the input procedure from step 2 onwards.
Make sure to open the stop valves after charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
BS2 SET
BS3 RETURN
BS3 RETURN
BS1 MODE
BS1 MODE
WARNING: ELECTRIC SHOCK
Caution when performing service to inverter
equipment
1 Do not open the electric component box cover for 10
minutes after the power supply is turned off.
2 Measure the voltage between terminals on the
terminal block for power supply with a tester and
confirm that the power supply is shut off.
In addition, measure the points, as shown in the figure
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC.
3 To prevent damaging the PC-board, touch a non-coated
metal part to eliminate static electricity before pulling out
or plugging in connectors.
4 Pull out junction connectors X1A, X2A, X3A, X4A
(X3A and X4A of REYQ14+16P are inside the electric
component box (2), refer to the wiring diagram) for the
fan motors in the outdoor unit before starting service
operation on the inverter equipment. Be careful not to
touch the live parts.
(If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and
cause electric shock.)
5 After the service is finished, plug the junction
connecter back in. Otherwise the error code E7 will be
displayed on the remote controller and normal
operation will not be performed.
For details refer to the wiring diagram labelled on the back
of the electric component box cover.
NOTE
Play it safe!
For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your
body before performing service.
A2P
A2P
A1P
A3P
TP1 TP2