Installation manual
2
REYQ8~16P8Y1B
VRVIII System air conditioner
4PW39996-1B
1.1. Indoor capacity range
The indoor units can be installed in the following range.
Always use appropriate indoor units compatible with R410A.
To learn which models of indoor units are compatible with
R410A, refer to the product catalogs.
Total capacity of indoor units
1.2. Standard supplied accessories
See location 1 in figure 18 for reference to where following
accessories are supplied with the unit.
See location 2 in figure 18 for reference to where following
accessories are supplied with the unit.
1.3. Optional accessories
To install the above outdoor unit, the following optional parts are also
required.
Refrigerant branching kit (for R410A only: Always use an appropriate
kit dedicated for your system.)
To select an optimum refrigerant branching kit, refer to "6. Refrigerant
piping" on page 4.
1.4. Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of
specifications.
2. MAIN COMPONENTS
For main components and function of the main components, refer to
the Engineering Data Book.
Outdoor unit Total capacity of indoor units
REYQ8 100~260
REYQ10 125~325
REYQ12 150~390
REYQ14 175~455
REYQ16 200~520
NOTE
If the total capacity of the connected indoor units
exceeds the capacity of the outdoor unit, cooling and
heating performance may drop when running the
indoor units.
Refer to the section on performance characteristics in
the Engineering Data Book for details.
Installation manual 1x
Operation manual 1x
Additional refrigerant charge label 1x
Installation information sticker 1x
Fluorinated greenhouse gases information sticker 1x
REYQ
8 10 12 14 16
Liquid accessory pipe (1) 1x 1x 1x 1x 1x
Liquid accessory pipe (2) 1x 1x 1x 1x 1x
Suction gas accessory pipe (1)
1x ————
—1x——
——1x1x 1x
Suction gas accessory pipe (2)
1x ————
—1x——
——1x1x 1x
High pressure/low pressure
accessory pipe (1)
1x ————
—1x1x—
———1x1x
High pressure/low pressure
accessory pipe (2)
1x ————
1x 1x
———1x1x
Accessory joint (angle of 90°) (1) 1x 1x 1x 1x 1x
Accessory joint (angle of 90°) (2) 1x 1x 1x 1x 1x
Accessory joint 1x ————
Ø22.2
Ø22.2
Ø28.6
Ø19.1
Ø22.2
Ø28.6
Ø15.9
Ø19.1
Ø19.1
Ø15.9
Ø19.1
Ø22.2
Ø25.4
Ø19.1
Refnet header Refnet joint
3 pipes 2 pipes 3 pipes 2 pipes
KHRQ23M29H KHRQ22M29H KHRQ23M20T KHRQ22M20T
KHRQ23M64H KHRQ22M64H KHRQ23M29T9 KHRQ22M29T
KHRQ23M75H KHRQ22M75H KHRQ23M64T KHRQ22M64T
KHRQ23M75T KHRQ22M75T