EasyManua.ls Logo

Daikin REYQ96 - Page 263

Daikin REYQ96
273 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Precautions for New Refrigerant (R-410A) SiUS39-602
252 Precautions for New Refrigerant (R-410A)
2 1/4"
5/16" (2min
2.5min)
2 No oil is used in pressure test of gauges.
For prevention of contamination
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2 Change in pressure
2 Change in service port diameter
7. Charge hose for R-410A
Specifications
2 Working pressure 737 psi (51.8 kg/cm
2
)
2 Rupture pressure 3685 psi (259 kg/cm
2
)
2 Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
2 Pressure proof hose
2 Change in service port diameter
2 Use of nylon coated material for HFC resistance
8. Weigher for refrigerant charge
Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
(Hose with ball valve)

Table of Contents