6 Electrical installation
Installation manual
11
RZASG100~140MUV/Y
Sky Air Advance-series
4P734658-1 – 2023.08
6.1 About electrical compliance
RZASG100~140MUV
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16A and ≤75A per phase.).
RZASG100~140MUY
Equipment complying with EN/IEC 61000‑3‑2 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current ≤16A per phase.).
6.2 Guidelines when connecting the
electrical wiring
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.8
M4 (earth) 1.2~1.4
M5 (X1M) 2.0~3.0
M5 (earth) 2.4~2.9
NOTICE
If limited space is available at the wire terminal, use
bended crimp-style ring terminals.
6.3 Specifications of standard wiring components
Component RZASG100~140MUV RZASG100~140MUY
100 125 140 100 125 140
Power supply cable MCA
(a)
22.7A 29.2A 28.5A 14.9A 15.7A 15.4A
Voltage range 220~240V 380~415V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with national wiring regulation
3-core cable 5-core cable
Wire size based on the current, but not less than:
Minimum 4.0mm
2
Minimum 2.5mm
2
Interconnection cable (indoor ↔
outdoor)
Voltage 220-240V
Wire size Only use harmonised wire providing double insulation and suitable for applicable
voltage.
4-core cable
Minimum 2.5mm
2
Recommended field fuse 25A 32A 16A
Earth leakage circuit breaker / residual current device Must comply with national wiring regulation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).
NOTICE
We recommend using solid (single-core) wires. If stranded
wires are used, slightly twist the strands to consolidate the
end of the conductor for either direct use in the terminal
clamp or insertion in a round crimp-style terminal. Details
are described in "Guidelines when connecting the electrical
wiring" in the installer reference guide.
6.4 To connect the electrical wiring to
the outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover.
2 Connect the interconnection cables and power supply as
follows:
c
a
d
e
1~ 50 Hz
220-240 V
3N~ 50 Hz
380-415 V
RZASG-MV RZASG-MY
L1 L2 L3
L1 L2 L3
N
b
b
a
a
a
I, II, III, IV Pair, twin, triple, double twin
M, S Master, slave
a Interconnection cables