EasyManua.ls Logo

Daikin Sky Air Advance Series - Units and Options; Identifying and Combining Units

Daikin Sky Air Advance Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Piping installation
Installation manual
8
RZASG100~140MUV/Y
Sky Air Advance-series
4P734658-1 – 2023.08
4.3.4 To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cables from scratching the paint (field supply).
4 Attach the ends of the cables.
5 Tighten the cables.
5 Piping installation
5.1 Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
5.1.1 To connect the refrigerant piping to the
outdoor unit
Keep the following in mind:
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical
damage.
You can route the refrigerant piping to the front, bottom, side or rear
of the unit.
a
b
c
d
a Front connection
b Bottom connection
c Side connection
d Rear connection
1 Remove the following plates:
For details, see "4.2.1To open the outdoor unit"[46].
Remove the service cover (a) and the piping intake front
plate (b).
In case the refrigerant piping is routed to the rear side of the
unit, also remove the piping intake rear plate (c).
a
c
b
a Service cover
b Piping intake front plate
c Piping intake rear plate
2 Remove the knockout hole(a) in the bottom plate or in the
piping intake plate by tapping on the attachment points with a
small flat screwdriver and a hammer. Optionally, cut out the slits
(b) with a metal saw.
b a b
b
b
b
b
a a
b
b
a
a Knockout hole for piping
b Slit
NOTICE
Precautions when making knockout holes:
Avoid damaging the casing and underlying piping.
After making the knockout holes, we recommend to
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
NOTICE
Avoid bending the bottom plate when removing the
knockout hole.
3 Connect the gas and liquid piping.
Connect the liquid piping (a) to the liquid stop valve (A).
Connect the gas piping (b) to the gas stop valve (B).

Table of Contents

Other manuals for Daikin Sky Air Advance Series

Related product manuals