6 Installation
Installer reference guide
14
RZA200+250D7Y1B
Sky Air Advance-series
4P573383-1 – 2019.04
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the metal can rust easily.
a
6.3.4 To install the outdoor unit
M12
6.3.5 To provide drainage
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
INFORMATION
If necessary, you can use a drain pan (field supply) to
prevent drain water from dripping.
NOTICE
If the unit CANNOT be installed fully level, always make
sure that the inclination is towards the backside of the unit.
This is required to guarantee proper drainage.
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150mm under the outdoor unit.
≥150 mm
Drain holes (dimensions in mm)
A
171 171758
43
48
288
451
613
776
408
414
349
214
111
(480~490)
107
B
B
C
D
=
E
A Discharge side
B Distance between anchor points
C Bottom frame
D Drain holes
E Knockout hole for snow
Snow
In regions with snowfall, snow might build up and freeze between the
heat exchanger and the casing of the unit. This might decrease the
operating efficiency.
INFORMATION
We suggest to install the optional bottom plate heater
(EKBPH250D7) when the unit is installed in cold climates.
6.3.6 To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cables from scratching the paint (field supply).
4 Attach the ends of the cables and tighten them.