6 Installation
Installer reference guide
24
RZA200+250D7Y1B
Sky Air Advance-series
4P573383-1 – 2019.04
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor
wire with round
crimp-style terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
O Allowed
X NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.8
M4 (earth) 1.2~1.4
M5 (X1M) 2.0~3.0
M5 (earth) 2.4~2.9
NOTICE
If limited space is available at the wire terminal, use
bended crimp-style ring terminals.
6.8.5 Specifications of standard wiring
components
Component RZA200 RZA250
Power supply
cable
MCA
(a)
18.6A 19.9A
Voltage range 380~415V
Phase 3N~
Frequency 50Hz
Wire sizes Must comply with applicable
legislation
Interconnection cables H05VV-U4G2.5
Recommended field fuse 20A
Earth leakage circuit breaker Must comply with applicable
legislation
(a)
MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
6.8.6 To connect the electrical wiring on the
outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "6.2.2 To open the outdoor
unit"[413].
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cables and power supply as
follows:
a
c
d
e
3N~ 50 Hz
380-415 V
L1 L2 L3
L1 L2 L3
N
b
a
a
a
I, II, III, IV Pair, twin, triple, double twin
M, S Master, slave
a Interconnection cables
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e User interface
INFORMATION
Some indoor units may need a separate power supply in
order to guarantee maximum capacity. See the installation
manual of the indoor unit.
c
d
a
d
b
a Interconnection cable
b Power supply cable
c Earth