4 About the units and options
Installer reference guide
8
RZA200+250D7Y1B
Sky Air Advance-series
4P573383-1 – 2019.04
3.2.2 To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
Carry the unit slowly as shown:
NOTICE
The cloth inside the left handle is intended to protect the
hand from being cut by the aluminium fins of the unit.
ONLY remove the cloth when the unit is completely
mounted:
3.2.3 To remove the accessories from the
outdoor unit
1
2
3
b
a c
d
e f
g
h i j k l
a General safety precautions
b Outdoor unit installation manual
c Cable tie
d Fluorinated greenhouse gases label
e Additional refrigerant charge label
f Addendum (LOT21)
g Liquid line piping — long
h Liquid line piping — short
i Liquid line piping — bend
j Gas line piping — short
k Gas line piping — long
l Gas line piping — bend
3.3 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The transportation stay protects the unit during transport. During
installation it must be removed.
Prerequisite: Open the service cover. See "6.2.2 To open the
outdoor unit"[413].
(10 N·m)
a
c
b
4
1
2
3
a Nut
b Transportation stay
c Spacer
1 Remove the nut (a) of the compressor mounting bolt.
2 Remove and discard the transportation stay (b).
3 Remove and discard the spacer (c).
4 Re-install the nut (a) of the compressor mounting bolt and
tighten to 10N•m of torque.
4 About the units and options
4.1 Overview: About the units and
options
This chapter contains information about:
Identifying the outdoor unit
Combining the outdoor unit with options
4.2 Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
4.2.1 Identification label: Outdoor unit
Location
Model identification
Example: R Z A 250 D7 Y1 B [*]
Code Explanation
R Air-cooled split outdoor unit
Z Inverter
A Refrigerant R32
200~250 Capacity class
D7 Model series
Y1 Power supply: 3N~, 380~415 V, 50 Hz