Daikin Sky Air Alpha RZAG100N2V1B - Refrigerant Piping Insulation

Daikin Sky Air Alpha RZAG100N2V1B
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 | Preparation
Installer reference guide
32
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
Requirement Limit
71 100 125+140
3 Maximum allowable piping length Pair: N/A
Twin: L1+L2+L3≤Limit 65m 85m
Triple: L1+L2+L3+L4≤Limit 85m
Double twin:
L1+L2+L3+L4+L5+L6+L7≤Limit
85m
4 Maximum branch piping length Pair: N/A 10m
Twin and triple: L2≤Limit
Double twin: L2+L4≤Limit
20m
5 Maximum difference between
branch lengths
Pair: N/A
Twin: L2–L3≤Limit 10m
Triple: L2–L4≤Limit 10m
Double twin:
L2–L3≤Limit
L4–L5≤Limit
L6–L7≤Limit
(L2+L4)–(L3+L7)≤Limit
10m
6 Maximum height between indoor
and outdoor
Pair, twin, triple and double twin:
H1≤Limit
30m
7 Maximum height between
indoors
Pair: N/A
Twin, triple and double twin:
H2≤Limit
0.5m
(a)
Parenthesised figure represents the equivalent length.
Example
If the system layout is as follows… Then the requirements are…
RZAG125
Triple:
L2
L3
L4
H1
H2
L1
Østandard
1 3m≤L1+L4
2 L1+L2≤85m (100m)
3 L1+L2+L3+L4≤85m
4 L2≤20m
5 L2–L4≤10m
6 H1≤30m
7 H2≤0.5m
6.3.2 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness

Table of Contents