7.7.5 Specifications of standard wiring components
Component V1 Y1
71 100 125~140 71 100 125 140
Power supply
cable
MCA
(a)
18.8A 23.3A 28.8A 12.3A 15.4A 15.7A 15.4A
Voltage range 220~240V 380~415V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with applicable legislation
Interconnection cables Minimum cable section of 2.5 mm² and applicable for 230 V
Recommended field fuse 20A 32A 16A
Earth leakage circuit breaker Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact
values).
7.7.6 To connect the electrical wiring to the outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1 Remove the service cover. See "7.2.2To open the outdoor unit"[434].
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Connect the interconnection cables and power supply as follows: