EasyManua.ls Logo

Daikin Sky Air Alpha RZAG100N2V1B - Guidelines When Connecting the Electrical Wiring

Daikin Sky Air Alpha RZAG100N2V1B
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 | Installation
Installer reference guide
59
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
7.7.4 Guidelines when connecting the electrical wiring
Keep the following in mind:
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b a
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.8
M4 (earth) 1.2~1.4
M5 (X1M) 2.0~3.0
M5 (earth) 2.4~2.9
NOTICE
If limited space is available at the wire terminal, use bended crimp-style ring
terminals.

Table of Contents