Field Settings SiBE18-821_C
142 Test Operation and Field Settings
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
25
Setting of external
low noise setting
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
∗
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
∗
About 24:00
khhhkhh
27
Night-time low noise
operation end setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
∗
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk ∗
ON
khhhhkh
29
Capacity
precedence setting
khkkkhk
OFF
khhhhhk ∗
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh
∗
80 % demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk
∗
ON
khhhhkh