SiBE18-821_C Field Settings
Test Operation and Field Settings 143
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Setting item 0 Display contents of “Various setting”
No. Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0 Various setting
lhhhhhh
See below
1 Cool / heat unified address
lhhhhhk
Lower 6 digits
2 Low noise/demand address
lhhhhkh
3 Not used
lhhhhkk
4 AIRNET address
lhhhkhh
5 Number of connected indoor units
lhhhkhk
7
Number of connected zone units
(excluding outdoor and BS unit)
lhhhkkk
8 Number of outdoor units
lhhkhhh
11
Number of zone units (excluding
outdoor and BS unit)
lhhkhkk
Lower 6 digits
12 Number of terminal blocks
lhhkkhh
Lower 4 digits:
upper
13 Number of terminal blocks
lhhkkhk
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
lhhkkkh
Error code table
Refer to page
326.
15
Contents of malfunction (1 cycle
before)
lhhkkkk
16
Contents of malfunction (2 cycle
before)
lhkhhhh
20 Contents of retry (the latest)
lhkhkhh
21 Contents of retry (1 cycle before)
lhkhkhk
22 Contents of retry (2 cycle before)
lhkhkkh
25
Normal judgment of outdoor units
PCB
lhkkhhk
Lower 2 digits:
kh
Abnormal
hk
Normal
hh
Unjudgment
EMG operation /
backup operation
setting
ON
lhhkhhh
OFF
lhhhhhh
Defrost select setting Short
lhhhkhh
Medium
lhhhlhh
Long
lhhhhhh
Te setting H
lhhhhkh
M
lhhhhlh
L
lhhhhhh
Tc setting H
lhhhhhk
M
lhhhhhl
L
lhhhhhh
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
Push the MODE (BS1) button and
returns to “Setting mode 1”.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals