18.2.8 Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The display and the settings differ depending on
the model.
Model Display Setting/value
5HP
7‑LEDs display
The seven LEDs give a binary representation of the setting/
value number.
8HP
7‑segments display
The three 7‑segments show the setting/value number.
For more information and advice about the impact of the following settings, see "18.3Energy saving and optimum
operation"[4113]:
• In case of 5HP: settings [2‑8], [2‑9], [2‑41] and [2‑42]
• In case of 8HP: settings [2‑8], [2‑9], [2‑81] and [2‑82]
Setting Value
(8HP) (5HP)
Description
[2‑8]
T
e
target temperature during cooling
operation.
0
(default
)
(default)
Auto
2 6°C
3 7°C
4 8°C
5 9°C
6 10°C
7 11°C
[2‑9]
T
c
target temperature during heating
operation.
0
(default
)
(default)
Auto
1 41°C
3 43°C
6 46°C