17 | Electrical installation
Installer and user reference guide
93
RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
Model Minimum circuit
ampacity
Recommended fuses
RKXYQ5 13.5A 16A
RKXYQ8 17.4A 20A
▪ Phase and frequency: 3N~50Hz
▪ Voltage: 380-415V
Transmission wiring
Transmission line section:
Transmission wiring Sheathed + shielded cable (2 wires)
Vinyl cords
0.75~1.25mm²
(using shielded cable for the
transmission wiring is mandatory for
5HP, and optional for 8HP)
Maximum wiring length
(= distance between compressor unit
and furthest indoor unit)
300m
Total wiring length
(= distance between compressor unit
and all indoor units, and between
compressor unit and heat exchanger
unit)
600m
If the total transmission wiring exceeds these limits, it may result in communication
error.
17.2 To connect the electrical wiring on the compressor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit, located on the switch box
cover).
▪ Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1 Remove the service covers of the compressor unit and the switch box. See
"15.2.2To open the compressor unit"[463].
2 Connect the transmission wiring as follows: