22 | Troubleshooting
Installer and user reference guide
130
RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
Main code Sub code Cause Solution
Warning: faulty wiring to Q1/Q2 Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
Malfunction code: faulty wiring to Q1/
Q2
Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
Too many indoor units are connected
to F1/F2 line
Bad wiring between outdoor and
indoor units
Check indoor unit amount and total
capacity connected.
System mismatch. Wrong type of
indoor units combined (R410A,
R407C, RA, etc). Indoor unit
malfunction
Heat exchanger unit malfunction
Check if other indoor units have
malfunction and confirm indoor unit
mix is allowed.
Check the transmission wiring to the
heat exchanger unit.
More than 1 heat exchanger unit
connected.
Check installation. Only 1 heat
exchanger unit can be installed.
Improper type of indoor units are
connected.
Mismatch of compressor unit and
heat exchanger unit.
Check the type of indoor units that
are currently connected. If they are
not proper, replace them with proper
ones.
Check if the compressor unit and heat
exchanger unit are compatible.
5HP heat exchanger unit connected. Check installation. Connect 8HP heat
exchanger unit.
Auto address malfunction
(inconsistency)
Mismatch of compressor unit and
heat exchanger unit.
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
Check if the compressor unit and heat
exchanger unit are compatible.
Auto address malfunction
(inconsistency)
Mismatch of compressor unit and
heat exchanger unit.
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
Check if the compressor unit and heat
exchanger unit are compatible.
The stop valves of the compressor
unit are left closed.
The piping and wiring of the specified
indoor unit or heat exchanger unit are
not connected correctly to the
compressor unit.
Open the stop valves on both the gas
and liquid side.
Confirm that the piping and wiring of
the specified indoor unit or heat
exchanger unit are connected
correctly to the compressor unit.