24 | Troubleshooting
Installer and user reference guide
147
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
Main code Sub code Cause Solution
Master Slave 1 Slave 2
— Unusual low pressure on
suction line
Close valve A immediately.
Push BS1 to reset. Check
following items before
retrying autocharge
procedure:
▪ Check if the gas side stop
valve is opened correctly.
▪ Check if the valve of the
refrigerant cylinder is
opened.
▪ Check if the air inlet and
outlet of the indoor unit are
not obstructed.
— Freeze-up prevention indoor
unit
Close valve A immediately.
Push BS1 to reset. Retry
autocharge procedure.
— Automatic charging nearly
finished
Prepare for autocharge
stopping.
— Automatic charging finished Finish autocharge mode.
Leak detection function related
— Unit is not prepared to
execute leak detection
operation
Refer to requirements to be
able to execute leak detection
operation.
— Indoor unit is out of
temperature range for leak
detection operation
Retry when ambient
conditions are satisfied.
— Outdoor unit is out of
temperature range for leak
detection operation
Retry when ambient
conditions are satisfied.
— Too low pressure was noticed
during leak detection
operation
Restart leak detection
operation.
— Indicates an indoor unit which
is not compatible with leak
detection functionality is
installed (e.g., RADX indoor
unit, Hydrobox, …)
Refer to requirements to be
able to execute leak detection
operation.