www.DaikinApplied.com 55 IOM 1281-2 • CENTRIFUGAL WATER CHILLERS
Figure 65: Settings View - Timers
Table 17: Timer Settings
Description Default Range Password 
Evap Recirculate 0.5 min 0.2 - 5 min M Time that evaporator pump must run before compressor start
Full Load Timer 59 sec 0 to 999 sec T Time compressor must load (without unloading) before vanes are considered fully open.
Start to Start Timer 40 min 2 to 60 min M Time required from a start to the next start
Stop to Start Timer 3 min 1 to 20 min M Time required from a stop to the next start
Dwell Time 0 min 0 to 99 min T Delay Time Alarms are passed to BAS to allow time for chiller to reset before disabled by BAS.
Prelube Timer 30 sec 10 to 240 sec T
Unload Timer 60 sec 5 to 300 sec T
Postlube Timer 30 sec 10 to 240 sec T
Figure 66: Settings View - Interface
Table 18: Unit Interface Settings
Description Default Range PW 
BAS Network Protocol NONE
NONE, Local, Remote, MODBUS,

Ethernet, BACnet MS/TP
M

BACnet IP: IP - Ethernet; BACnet Ethernet: Ethernet; BACnet MS/TP: RS485
NOTE: It is likely that the chiller will contain the factory settings for date and time; therefore, it is important to verify or change


Applied to answer questions about unit operation or to assist in possible future upgrades of software.