© Danfoss A/S (AC-MCI/MWA), 2012-05  DKRCI.PD.SC0.C3.02 / 520H5687 13
Liquid Level Sensor, AKS 4100/4100U
•   Connect the device to the power supply 
  (see the product instruction for detail on  
  electrical installation/connection).
•   Press   3 times.
•   Press   
•   Press 
 
or 
 
to select between SINGLE 
  or COAXIAL. Choose COAXIAL and  
 press   to conrm. 
•   Press   (YES) to conrm
•   Press   to change GAS EPS.R. 
  (Select the correct value from the tables  
  on page 16) 
 Press   to change cursor- 
 position. 
  Press 
 
to decrease the value or 
 
to 
  increase the value.
AKS 4100
QUICK SETUP ?
YES               NO
AKS 4100
PROBE TYPE
SINGLE CABLE
•   Press   to conrm.
•   Press 
 
to change the PROBE LENGTH. 
 Press 
 
to change the position of the  
 cursor.  
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm. 
•   Press 
 
to change of SCALE 4 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm. 
•   Press 
 
to change of SCALE 20 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm.
•   Wait for QUICK SETUP to complete.  
  Count down from 8 sec.
•   Press   to conrm.
•   Press 
 
or 
 
to select between  
  STORE NO or STORE YES.  
 Press   to conrm. 
  Default screen appears:
  Quick Setup  completed
You have the possibility of checking your 
settings by pressing 
 
twice.
Press        to return to default screen.
Quick Setup (all values below are only examples)
•   Connect the device to the power supply
•   Press   3 times.
•   Press   
•   Press 
 
or 
 
to select between SINGLE 
  or COAXIAL. Choose COAXIAL and  
 press   to conrm.
•   Press 
 
(NO) to conrm
AKS 4100
QUICK SETUP ?
YES               NO
AKS 4100
PROBE TYPE
SINGLE CABLE
•   Press 
 
to change the PROBE LENGTH. 
 Press 
 
to change the position of the  
 cursor.  
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm. 
•   Press 
 
to change of SCALE 4 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm. 
•   Press 
 
to change of SCALE 20 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm.
•   Wait for QUICK SETUP to complete.  
  Count down from 8 sec.
•   Press   to conrm.
•   Press 
 
or 
 
to select between  
  STORE NO or STORE YES.  
 Press   to conrm. 
  Default screen appears:
  Quick Setup completed
AKS 4100
PROBE  LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP 
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
When CO
2
 is used:
For all other refrigerants:
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP 
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE  LENGTH
05000 mm
COAXIAL version
AKS 4100
QUICK SETUP ?
YES                     NO
AKS 4100
QUICK SETUP ?
YES                     NO
AKS 4100
COAXIAL 2200 mm
(0 %) 4 mA 1900 mm
(100 %) 20 mA 70 mm