14  DKRCI.PD.SC0.C3.02 / 520H5687  © Danfoss A/S (AC-MCI/MWA), 2012-05
Liquid Level Sensor, AKS 4100/4100U
  Default screen
•   Press   
•   Press   
•   Press   
  Enter password: 
 
         
   
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.5.0
APLICATION
AKS 4100
2.5.1
TRACING VEL.
•   Press   4 times. 
•   Press   
•   Press   2 times. 
•   Press 
 
to change GAS EPS.R. 
  (Select the correct value from the tables  
  on page 16) 
 Press   to change cursor- 
 position. 
  Press 
 
to decrease the value or 
 
to 
  increase the value.
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
GAS EPS. R
1.066
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
•   Press   to conrm.
•   Press   3 times.
•   Press 
 
or 
 
to select between  
  STORE NO or STORE YES.  
  Select STORE YES by pressing   
  Default screen appears:
  Entering the dielectric constant of  
  refrigerant gas completed
Entering refrigerant dielectric gas constant (all values below are only examples)
Optional Procedure
If the temperature condition in the stand pipe is known, a constant (dielectric constant of the refrigerant gas) can be entered  
(parameter 2.5.3 GAS EPS.R), in order to obtain lower Top and Bottom Dead Zone values (see pages 7 and 8).
  Default screen
•   Press   
•   Press   
•   Press   
  Enter password: 
 
         
   
AKS 4100
DISTANCE
5000 mm
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.2.0
TESTS
AKS 4100
2.2.1
SET OUTPUT
AKS 4100
SET OUTPUT
3.5 mA
AKS 4100
SET OUTPUT
8 mA
AKS 4100
DISTANCE
5000 mm
•   Press 
•   Press 
•   Press 
•   Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to conrm.
•    Press   4 times to return to default 
screen.
  Default screen appears:
  Force mA completed and disabled
Forcing mA output (all values below are only examples)
CABLE and COAXIAL version
AKS 4100
1.0.0
QUICK START
AKS 4100
QUICK SETUP ?
YES                     NO
AKS 4100
QUICK SETUP ?
YES                     NO