Parameter list VLT 5000 Flux
0
-1
2
0
0
0
0
PNU Parameter Factory setting Range Changes Conversion
# description during Index
operation
400 Brake function/overvoltage control Off Yes No 5
401 Brake resistor, ohm Depends on the unit Yes No 6
402 Brake power limit, kW Depends on the unit Yes No 6
403 Power monitoring Warning Yes No 5
404 Brake check Off Yes No 5
405 Reset function Manual reset Yes Yes 5
406 Automatic restart time 5 sec. 0 - 10 sec. Yes Yes 5
409 Trip delay torque 5 sec. 0 - 10 sec.
417 Speed PID proportional gain 0.015 0.000 - 5000 Yes Yes -3 6
418 Speed PID integration time 200 ms 2.00 - 20.000 ms Yes Yes -4 7
419 Speed PID differentiation time 0 ms 0.00 - 200.00 ms Yes Yes -4 6
420 Speed PID diff. gain ratio 10.0 5.0 - 50.0 Yes Yes -1 6
421 Speed PID low-pass filter 2 ms 1-10 ms Yes Yes -4 6
445 Flying start Disable Yes Yes 0 5
458 LC-filter connected No 0-1 No Yes 0 5
459 Capacity LC-filter 2 µF 0.1-100 µFNoYes-16
460 Inductance LC-filter 7 mH 0.1-100 mH No Yes -1 6