Parameter list
PNU Parameter Factory setting Range Changes Conversion
# description during Index
operation
200 Output frequency Only clockwise, No Yes
range/direction 0-132 Hz
201 Output frequency low limit 0.0 Hz 0.0 - f
MAX
Yes Yes
202 Output frequency high limit 66 / 132 Hz f
MIN
- par. 200 Yes Yes
203 Reference/feedback area Min - max Yes Yes
204 Minimum reference 0.000 -100,000.000-Ref
MAX
Yes Yes
205 Maximum reference 50.000 Ref
MIN
-100,000.000 Yes Yes
206 Ramp type Linear Yes Yes
207 Ramp-up time 1 Depends on unit 0.05 - 3600 Yes Yes
208 Ramp-down time 1 Depends on unit 0.05 - 3600 Yes Yes
209 Ramp-up time 2 Depends on unit 0.05 - 3600 Yes Yes
210 Ramp-down time 2 Depends on unit 0.05 - 3600 Yes Yes
211 Jog ramp time Depends on unit 0.05 - 3600 Yes Yes
212 Quick stop ramp-down time Depends on unit 0.05 - 3600 Yes Yes
213 Jog frequency 10.0 Hz 0.0 - par. 202 Yes Yes
214 Reference function Sum Yes Yes
215 Preset reference 1 0.00 % - 100.00 - 100.00 % Yes Yes
216 Preset reference 2 0.00 % - 100.00 - 100.00 % Yes Yes
217 Preset reference 3 0.00 % - 100.00 - 100.00 % Yes Yes
218 Preset reference 4 0.00 % - 100.00 - 100.00 % Yes Yes
219 Catch up/slow down value 0.00 % 0.00 - 100 % Yes Yes
220
221 Torque limit for motor mode 160 % 0.0 % - xxx % Yes Yes
222 Torque limit for regenerative operation 160 % 0.0 % - xxx % Yes Yes
223 Warning: Low current 0.0 A 0.0 - par. 224 Yes Yes
224 Warning: High current I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes Yes
225 Warning: Low frequency 0.0 Hz 0.0 - par. 226 Yes Yes
226 Warning: High frequency 132.0 Hz Par. 225 - par. 202 Yes Yes
227 Warning: Low feedback -4000.000 -100,000.000 - par. 228 Yes
228 Warning: High feedback 4000.000 Par. 227 - 100,000.000 Yes
229 Frequency bypass, bandwidth OFF 0 - 100 % Yes Yes
230 Frequency bypass 1 0.0 Hz 0.0 - par. 200 Yes Yes
231 Frequency bypass 2 0.0 Hz 0.0 - par. 200 Yes Yes
232 Frequency bypass 3 0.0 Hz 0.0 - par. 200 Yes Yes
233 Frequency bypass 4 0.0 Hz 0.0 - par. 200 Yes Yes
234 Motor phase monitor Enable Yes Yes
0
-1
-1
0
-3
-3
0
-2
-2
-2
-2
-2
-2
-1
0
-2
-2
-2
-2
-2
-1
-1
-1
-1
-1
-1
-3
-3
0
-1
-1
-1
-1
0
5
6
6
5
4
4
5
7
7
7
7
7
7
6
5
3
3
3
3
6
6
6
6
6
6
6
4
4
6
6
6
6
6
5
4-Setup
Data
type
■ Parameter list VLT 5000