MG.90.D1.02 – VLT is a registered Danfoss trademark
60
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
Parameter list
Changes during operation
"Yes" means that the parameter can be changed,
while the VLT frequency converter is in operation.
"No" means that the VLT frequency converter must
be stopped before a change can be made.
4-Setup
"Yes" means that the parameter can be program-
med individually in each of the four setups, i.e. the
same parameter can have four different data
values.
"No" means that the data value will be the same in
all four setups.
Conversion index
This number refers to a conversion figure to be
used when writing or reading by means of a VLT
frequency converter.
Conversion index Conversion factor
74 0.1
2 100
110
01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
Data type
… shows the type and length of the telegram
.
Data type Description
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Text string
PNU Parameter Factory setting Range Changes Conversion
# description during Index
operation
300 Terminal 16, input Reset Yes Yes
301 Terminal 17, input Freeze reference Yes Yes
302 Terminal 18 Start, input Start Yes Yes
303 Terminal 19, input Reversing Yes Yes
304 Terminal 27, input Coasting stop, inverse Yes Yes
305 Terminal 29, input Jog Yes Yes
306 Terminal 32, input Choice of setup, msb/speed up Yes Yes
307 Terminal 33, input Choice of setup, lsb/speed down Yes Yes
308 Terminal 53, analog input voltage Reference Yes Yes
309 Terminal 53, min. scaling 0.0 V 0.0 - 10.0 V Yes Yes
310 Terminal 53, max. scaling 10.0 V 0.0 - 10.0 V Yes Yes
311 Terminal 54, analog input voltage No operation Yes Yes
312 Terminal 54, min. scaling 0.0 V 0.0 - 10.0 V Yes Yes
313 Terminal 54, max. scaling 10.0 V 0.0 - 10.0 V Yes Yes
314 Terminal 60, analog input current Reference Yes Yes
315 Terminal 60, min. scaling 0.0 mA 0.0 - 20.0 mA Yes Yes
316 Terminal 60, max. scaling 20.0 mA 0.0 - 20.0 mA Yes Yes
317 Time out 10 sec. 1 - 99 sec. Yes Yes
318 Function after time out Off Yes Yes
319 Terminal 42, output 0 - I
MAX
Þ 0-20 mA Yes Yes
320 Terminal 42, output, pulse scaling 5000 Hz 1 - 32000 Hz Yes Yes
321 Terminal 45, output 0 - f
MAX
Þ 0-20 mA Yes Yes
322 Terminal 45, output, pulse scaling 5000 Hz 1 - 32000 Hz Yes Yes
323 Relay 01, output Ready - no thermal warning Yes Yes
324 Relay 01, ON delay 0.00 sec. 0.00 - 600 sec. Yes Yes
325 Relay 01, OFF delay 0.00 sec. 0.00 - 600 sec. Yes Yes
326 Relay 04, output Ready - remote control Yes Yes
327 Pulse reference, max. frequency 5000 Hz Yes Yes
328 Pulse feedback, max. frequency 25000 Hz Yes Yes
329 Encoder feedback pulse/rev. 1024 pulses/rev. 1 - 4096 pulses/rev. Yes Yes
330 Freeze reference/output function No operation Yes No
345 Encoder loss timeout 0 sec. 0 - 60 sec No Yes
346 Encoder loss function OFF Yes Yes
0
0
0
0
0
0
0
0
0
-1
-1
0
-1
-1
0
-4
-4
0
0
0
0
0
0
0
-2
-2
0
0
0
0
0
-1
0
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
6
5
6
5
6
6
5
6
6
6
5
6
5
4-Setup
Data
type
■ Parameter list VLT 5000