EasyManua.ls Logo

Danfoss AK-CC55 - Temperature Control and Monitoring; Thermostat Bands

Danfoss AK-CC55
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Menu survey
SW = 2.0x
Menu set via display
R-W
If the operation is limited by a setting of one or more passwords, reading and setting the
parameter will be limited to:
R: This setting can be seen with password no. _ or higher.
W: This setting can be performed with password no. _ or higher (3 is the highest level).
*) Always required that the regulating is stopped, r12=0)
**) Always required that the regulating is stopped and set to manual service, r12= -1)
Parameter Wiring diagram pages 2-4
Min. value Max. value
Factory
setting
Actual
setting
Function R-W Code 1 2 3 4 5 6 7 8 9
Normal operation
Temperature (setpoint) 0-0 r00 1 1 1 1 1 1 1 1 1 "r03" "r02" 2
Thermostat
Differential
1-2 r01 1 1 1 1 1 1 1 1 1 0.1 K 20 K 2
Max. limitation of setpoint setting
0-2 r02 1 1 1 1 1 1 1 1 1 "r03" 50 °C 50
Min. limitation of setpoint setting
0-2 r03 1 1 1 1 1 1 1 1 1 -50 °C "r02" -50
Temperature unit (°C/°F)
1-2 r05 1 1 1 1 1 1 1 1 1 0/°C 1/F 0/°C
Correction of the signal from S4
1-2 r09 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
Correction of the signal from S3
1-2 r10 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
Manual service, stop regulation, start regulation (-1,
0, 1)
0-2 r12 1 1 1 1 1 1 1 1 1 -1 1 0
Displacement of reference during night operation
1-2 r13 1 1 1 1 1 1 1 1 1 -50 K 50 K 0
Define thermostat function
1=ON/OFF, 2=Modulating
1-2 r14 1 1 1 1 1 1 1 1 1 1 2 1
Definition and weighting, if applicable, of thermostat
sensors - S4% (100%=S4, 0%=S3)
1-2 r15 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Time between melt periods 1-2 r16 1 1 1 1 1 1 1 1 1 0 hrs 10 hrs 1
Duration of melt periods 1-2 r17 1 1 1 1 1 1 1 1 1 0 min. 30 min. 5
Temperature setting for thermostat band 2 . As dif-
ferential use r01
0-2 r21 1 1 1 1 1 1 1 1 1 -50 °C 50 °C 2
Correction of the signal from S3B 1-2 r53 1 1 -10 K 10 K 0
Correction of the signal from S6 1-2 r59 1 1 1 1 1 1 1 -10 K 10 K 0
Definition and weighting, if applicable, of thermostat
sensors when night cover is on. (100%=S4, 0%=S3)
1-2 r61 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Heat function
Neutral zone between refrigeration and heat function
1-2 r62 1 0 K 50 K 5
Time delay at switch between refrigeration and heat
function
1-2 r63 1 0 min. 240 min. 240
Food type: use settings listed in table. 1-2* r89 1 1 1 1 1 1 1 1 1 0 5 0
Min. limit for S4 temperature 1-2 r98 1 1 1 1 1 1 1 1 1 -50 °C 50 °C -50
Alarms
Delay for temperature alarm 1-2 A03 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Delay for door alarm 1-2 A04 1 1 1 1 1 1 1 1 1 0 min. 240 min. 60
Delay for temperature alarm after defrost 1-2 A12 1 1 1 1 1 1 1 1 1 0 min. 240 min. 90
High alarm limit for thermostat 1 1-2 A13 1 1 1 1 1 1 1 1 1 -50 °C 50 °C 8
Low alarm limit for thermostat 1 1-2 A14 1 1 1 1 1 1 1 1 1 -50 °C 50 °C -30
High alarm limit for thermostat 2 1-2 A20 1 1 1 1 1 1 1 1 1 -50 °C 50 °C 8
Low alarm limit for thermostat 2 1-2 A21 1 1 1 1 1 1 1 1 1 -50 °C 50 °C -30
High alarm limit for sensor S6 at thermostat 1 1-2 A22 1 1 1 1 1 1 1 -50 °C 50 °C 8
Low alarm limit for sensor S6 at thermostat 1 1-2 A23 1 1 1 1 1 1 1 -50 °C 50 °C -30
High alarm limit for sensor S6 at thermostat 2 1-2 A24 1 1 1 1 1 1 1 -50 °C 50 °C 8
Low alarm limit for sensor S6 at thermostat 2 1-2 A25 1 1 1 1 1 1 1 -50 °C 50 °C -30
© Danfoss | DCS (vt) | 2019.07
10 | AN294432763974en-000201

Other manuals for Danfoss AK-CC55

Related product manuals