Additional information:
User Guide: RS8KG102
ADAP-KOOL®
Operating status (Measurement)
The controller goes through some regulating situations where it is just waiting for the next 
sequence of the regulation. To make these “why is nothing happening” situations visible, you can 
see an operating status on the display. Push the info button for 3 seconds to see status. If there 
is a status code, it will be shown on the display. The individual status codes have the following 
meanings:
Ctrl. state:
(Shown in all menu displays)
Normal regulation S0 0
Waiting for end of the coordinated defrost S1 1
When the compressor is operating it must run for at least x minutes S2 2
When the compressor is stopped, it must remain stopped for at least x minutes S3 3
The evaporator drips off and waits for the time to run out S4 4
Refrigeration stopped by main switch. Either with r12 or a DI-input S10 10
Refrigeration stopped by thermostat S11 11
The refrigeration is stopped due to too low S4 temperature S12 12
Defrost sequence. Defrost in progress S14 14
Defrost sequence. Fan delay — water attaches to the evaporator S15 15
Refrigeration stopped due to open ON input or stopped regulation S16 16
Door is open. DI input is open S17 17
Melt function in progress. Refrigeration is interrupted S18 18
Modulating thermostat control S19 19
Emergency cooling *) S20 20
Adaptive control of superheat S23 23
Start-up phase 1. Signal reliability from sensors is controlled S24 24
Manual control of outputs S25 25
No refrigerant selected S26 26
Appliance cleaning S29 29
Forced cooling S30 30
Delay on outputs during start-up S32 32
Case shutdown S45 45
Operation with adaptive liquid control S48 48
Other displays:
Defrost in progress / First cooling after the defrost where the temperature is still above the 
thermostat band.
-d-
Password required. Set password  PS
Regulation is stopped via main switch or case cleaning OFF
The main switch is set to service/manual operation SEr
*) Emergency cooling will take effect when there is lack of signal from a defined S3 or S4 sensor 
or signal from the pressure transmitter is outside signal range. The regulation will continue 
with a registered average cut-in frequency. There are two registered values – one for day 
operation and one for night operation.