5.10.2Temp.monitor.
MENU>Settings>Alarm
Upperdifference
1x147
Thealarmisactivatediftheactualflow/ducttemperatureincreasesmore
thanthesetdifference(acceptabletemperaturedifferenceabovethedesired
flow/ducttemperature).Seealso'Delay'.
SeeAppendix“ParameterIDoverview
OFF:
Therelatedalarmfunctionisnotactive.
Value:
Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
Upperdifference
X
=
Time
Y
=
Temperature
#1#
=
Upperdifference
#2#
=
Desiredflowtemperature
MENU>Settings>Alarm
Lowerdifference
1x148
Thealarmisactivatediftheactualflow/ducttemperaturedecreasesmore
thanthesetdifference(acceptabletemperaturedifferencebelowthedesired
flow/ducttemperature).Seealso'Delay'.
SeeAppendix“ParameterIDoverview
OFF:
Therelatedalarmfunctionisnotactive.
Value:
Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
Lowerdifference
X
=
Time
Y
=
Temperature
#1#
=
Lowerdifference
#2#
=
Desiredflowtemperature
VI.GU.L2.02
©Danfoss|2017.09|151
OperatingGuideECLComfort210/296/310,applicationA275/A375

Other manuals for Danfoss ECL Comfort 310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 310 and is the answer not in the manual?

Danfoss ECL Comfort 310 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 310
CategoryController
LanguageEnglish

Related product manuals