MENU>Settings>Alarm
Delay,example
1x149
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is
presentforalongertimethanthesetdelay(inminutes),thealarmfunction
isactivated.
SeeAppendix“ParameterIDoverview
Value:
Thealarmfunctionwillbeactivatedifthealarm
conditionremainsafterthesetdelay.
Delay,example
X
=
Time
Y
=
Temperature
#1#
=
Lowerdifference
#2#
=
Desiredflowtemperature
#3#
=
Actualflowtemperature
#4#
=
Delay(ID1x149)
MENU>Settings>Alarm
Lowesttemp.
1x150
Thealarmfunctionwillnotbeactivatedifthedesiredflow/duct
temperatureislowerthanthesetvalue.
SeeAppendix“ParameterIDoverview
Ifthecauseofthealarmdisappears,thealarmindicationandoutput
alsodisappear.
152|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375