MENU>Commoncontroller>System>M-busconfig.
Scantime
Energymeter1(2,3,4,5)
6002
CircuitSettingrange
Factorysetting
-
1-3600sec60sec
Settingthescanningtimeforacquiringdataofconnectedenergy
meter(s).
Iftheenergymeterisbatterypowered,thescantimeshouldbesetto
ahighvaluetopreventatoofastbatterydraining.
Oppositely,iftheflow/powerlimitationfunctionisusedintheECL
Comfort310,thescantimeshouldbesettoalowvalueinorderto
havequicklimitation.
MENU>Commoncontroller>System>M-busconfig.
ID
Energymeter1(2,3,4,5)
Read-out
CircuitSettingrange
Factorysetting
---
Informationabouttheenergymeter'sserialno.
MENU>Commoncontroller>System>Energymeters
Energymeter1(2,3,4,5)
Read-out
CircuitSettingrange
Factorysetting
-
0-40
Informationfromactualenergymeterabout,forexample,ID,
temperatures,flow/volume,power/energy.
Theshowninformationdependsonthesettingsmadeinthe“M-bus
config. ”menu.
6.8.7Rawinputoverview
Measuredtemperatures,inputstatusandvoltagesaredisplayed.
Inaddition,adetectionofmalfunctionscanbechosenforactivated
temperatureinputs.
Monitoringthesensors:
Choosethesensorwhichmeasuresatemperature,forexamplethe
S5.Whenthedialispressed,amagnifyingglass
appearsinthe
selectedline.TheS5temperatureisnowbeingmonitored.
Alarmindication:
Shouldtheconnectiontothetemperaturesensorbedisconnected,
short-circuitedorthesensoritselfbedefective,thealarmfunction
isactivated.
Inthe"Rawinputoverview"analarmsymbol
isshownatthe
defectivetemperaturesensorinquestion.
Resettingthealarm:
Choosethesensor(Snumber)forwhichyouwanttoclearthe
alarm.Pressthedial.Themagnifyingglass
andalarmsymbols
disappear.
Whenthedialispressedagain,themonitoringfunctionis
reactivated.
Thetemperaturesensorinputshaveameasuringrangefrom-60...
150°C.
Ifatemperaturesensororitsconnectionbreaks,thevalueindication
is"--".
Ifatemperaturesensororitsconnectionisshort-circuited,thevalue
indicationis"---".
168|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375