OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Stab.time(stabilizationtime)
1x313
CircuitSettingrange
Factorysetting
All
**
Settingofmax.timetoelapsebetweenpumpstartcommandandfeedback
fromdifferentialpressureswitch.
Ifthedifferentialpressureswitchdoesnotgivefeedbackwithinthesettime,
thealarmwillbeactivatedandtheotherpumpwillgetastartcommand.



MENU>Settings>Pumpcontrol
Chan.-overtime(change-overtime)
1x314
CircuitSettingrange
Factorysetting
All
**
Settingoftimetoelapsebetweenthepumpstopcommandforonepump
andthestartcommandfortheotherpump.
Thechange-overtimecanensurethatapumpisstoppedefcientlybefore
theotherpumpstarts.

OFF:

1...99:

X
=
Time
#1#
=
PumpP3
#2#
=
PumpP5
#3#
=
Change-overtime(sec.)




Example:

OFF:


ON:




