EasyManua.ls Logo

Danfoss ECL Comfort A368

Danfoss ECL Comfort A368
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Retrytime
1x310
CircuitSettingrange
Factorysetting
All
**
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated
forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe
alarmandtheretrytimeforrepeatedpumpstart.

OFF:


1...99:


MENU>Settings>Pumpcontrol
MENU>Settings>Rellwater
Change,duration
1x311
CircuitSettingrange
Factorysetting
All
**
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace
atthetimesetin'Changetime'.

X
=
Time
#1#
=
PumpP3
#2#
=
PumpP5
#3#
=
Change,duration(days)
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
1x312
CircuitSettingrange
Factorysetting
All
**
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided
into24hours.Thefactorysettinghereis12whichmeans12:00(noon).

X
=
Time
#1#
=
PumpP3
#2#
=
PumpP5
#3#
=
Changetime(clocktime)




Related product manuals