OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Retrytime
1x310
CircuitSettingrange
Factorysetting
All
**
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated
forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe
alarmandtheretrytimeforrepeatedpumpstart.
OFF:
1...99:
MENU>Settings>Pumpcontrol
MENU>Settings>Rellwater
Change,duration
1x311
CircuitSettingrange
Factorysetting
All
**
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace
atthetimesetin'Changetime'.
X
=
Time
#1#
=
PumpP3
#2#
=
PumpP5
#3#
=
Change,duration(days)
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
1x312
CircuitSettingrange
Factorysetting
All
**
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided
into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
X
=
Time
#1#
=
PumpP3
#2#
=
PumpP5
#3#
=
Changetime(clocktime)