ECAMENU>ECAsystem>ECAcommunication
Connectionaddr.(Connectionaddress)
Settingrange
Factorysetting
1…9/15
15
SettingoftheaddresstowhichECLcontrollerthe
communicationmustrun.
1..9:
Slavecontrollers.
15:
Mastercontroller.
AnECA30/31caninanECL485bussystem(master–slave)besetto
communicate,onebyone,withalladdressedECLcontrollers.
Example:
Connectionaddr.=15:TheECA30/31communicateswiththe
ECLmastercontroller.
Connectionaddr.=2:TheECA30/31communicateswiththe
ECLcontrollerwithaddress2.
Theremustbeamastercontrollerpresentinordertobroadcasttime
anddateinformation.
AnECLComfortcontroller210/310,typeB(withoutdisplayanddial)
cannotbeassignedtotheaddress0(zero).
ECAMENU>ECAsystem>ECAoverride
Overrideaddr.(Overrideaddress)
Settingrange
Factorysetting
OFF/1…9/15OFF
Thefeature'Override'(toextendedcomfortor
savingperiodorholiday)mustbeaddressedtothe
ECLcontrollerinquestion.
OFF:
Overridenotpossible.
1..9:
Addressofslavecontrollerforoverride.
15:
Addressofmastercontrollerforoverride.
Extendedsavingmode:
Extendedcomfortmode:
Holidayawayfromhome:
Overridefunctions:
Holidayathome:
OverridebymeansofsettingsinECA30/31arecancellediftheECL
Comfortcontrollergoesintoholidaymodeorischangedtoanother
modethanscheduledmode.
ThecircuitinquestionforoverrideintheECLcontrollermustbein
scheduledmode.
Seealsotheparameter'Overridecircuit'.
176|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375