OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
1x014
CircuitSettingrange
Factorysetting
All
**
Optimizesthestartandstoptimesforthecomforttemperatureperiodto
obtainthebestcomfortatthelowestenergyconsumption.
Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower
theoutdoortemperature,thelatertheheatingcut-out.
Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The
calculatedstartandstoptimesarebasedonthesettingoftheoptimizing
timeconstant.
OFF:
10...59:
LeftdigitHeataccumulationofthe
building
Systemtype
Rightdigit
DimensioningtemperatureCapacity
Dimensioningtemperature:
Example