OperatingGuideECLComfort310,applicationA368
MENU>Settings>Application
MENU>Settings>Optimization
Totalstop
1x021
CircuitSettingrange
Factorysetting
All
**
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.

OFF:




ON:



Totalstop=OFF
Totalstop=ON
X
=
Time
Y
=
Desiredowtemperature
#1#
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
=
Frostprotection


MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
1x026
CircuitSettingrange
Factorysetting
All
**
Disabletheoptimizedstoptime.

OFF:

ON:

Example:OptimizationofComfortfrom07:00-22:00
X
=
Time
#1#
=
Schedule
#2#
=
Prestop=OFF
#3#
=
Prestop=ON
#4#
=
Optimizedstart
#5#
=
Optimizedstop


