Installation Guide GreenCon RC-C2/C4
GB
VIE2C32P Danfoss Heating Solutions
Parameter Denition Setting range
Factory
setting
P10
Default cooling
temperature for
ECO mode
5-35°C 28°C
P11
Fan speed when
reaching setting
temperature (DA/
DB conguration)
01: Low (DA);
02: Stop (DB) 02
P12 Clock
01: 24hour;
02: 12hour
01
P13
Display room
temperature after
turned o
01: OFF; 02: ON 01
P14
Save user set up
when powered o.
01: ON; 02: OFF 01
P15 Auto switch
between heating
and cooling
01:Close
02: Open
01
P16 deadBand for
Normal Mode
0.5°C-5°C 1°C
P17 deadBand for ECO
Mode
5°C-10°C 5°C
P18
Floor/radiator for
heating & fan coil
for cooling
01: O; 02 On 01