9. Parameter setting
Long press “M” for 6 seconds to enter param-
eter setting mode.Then, short press “M” to
select parameter; press “ < ” or “ > ” to adjust
value.
Parameter Denition Setting range
Factory
setting
P01 Programming
function On/O
01: O;02:5/2
days 4 event
01
P02 Timer ON/OFF 01:ON;02:OFF 01
P03 Maximum room
temperature
setting
5-35°C 30°C
P04 Minimum room
temperature
setting
5-35°C 5°C
P05 Frost protection 01: ON; 02: OFF 01
P06
Frost protection
temperature
5-17°C 5°C
P07
Default heating
temperature
5-35°C 20°C
P08
Default cooling
temperature
5-35°C 25°C
P09
Default heating
temperature for
ECO mode
5-35°C 15°C