EasyManuals Logo

Danfoss ICAD 600A Installation Guide

Danfoss ICAD 600A
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
© Danfoss | DCS (ms) | 2020.01
AN19798642980802-000701 | 5
Parameter list - Valid from: (¡58:14, ¡59:45) and onwards
Description
ICAD
parameter
Min Max
Factory
Setting
Stored Unit
Pass
word
Comments
OD (Opening degree) - 0 100 % -
ICM/ICMTS valve Opening Degree (CVE pressure setting) is displayed during normal
operation.
Running display value (see ¡01, ¡05).
Main Switch ¡01 1 2 1
- No
Internal main switch
1: Normal operation
2: Manual operation. Valve Opening Degree will be flashing. With the down
arrow and the up arrow push buttons the OD can be entered manually.
Mode ¡02 1 2 1
- No
Operation mode
1: Modulating – ICM, ICMTS & CVE positioning according to Analog Input (see ¡03)
2: ON/OFF - ICM only. Operating the ICM valve like an ON/OFF solenoid valve
controlled via Digital Input. See also ¡09.
3: Neutralzone / 3 point control - ICM only. Increase/Decrease Opening Degree by
Digital Input. See fig. 9
AI signal ¡03 1 4 2
- No
Type of AI signal from external controller
1: 0 – 20 mA
2: 4 – 20 mA
3: 0 – 10 V
4: 2 – 10 V
Speed
In Modulating Mode
Opening/closing
speed
In ON/OFF Mode
Opening speed
In Neutralzone/
3 point control
Opening speed = 10
¡04 1 100 50/ 100
- No
Speed can be decreased. Max. speed is 100 % - Not active in manual operation (¡01 = 2)
For CVE the speed should not exceed 50 (factory setting)
If ¡26= 1 - 3 then factory setting =100
If ¡26= 4 - 10 then factory setting =50
If the valve is opening and (¡04 < = 33) or the valve is closing and (¡14 < = 33)
=> Low is displayed.
If the valve is opening and (33 < If ¡04 < = 66) or the valve is closing and (33 < If ¡14 < = 66)
=> Med is displayed.
If the valve is opening and (¡04 > = 67) or the valve is closing and (¡14 > = 67)
=> High is displayed"
Automatic calibration ¡05 0 2 0 - No
Not active before ¡26 has been operated.
Always auto reset to 0.
CA will flash in the display during calibration,
if Enter push button has been activated for two seconds
0: No Calibration
1: Normal forced calibration - CA flashing slowly
2: Extended calibration – CA flashing rapidly"
AO signal ¡06 0 2 2
- No
Type of A0 signal for ICM valve position
0: No signal
1: 0 – 20 mA
2: 4 – 20 mA
Failsafe ¡07 1 4 1
- No
Define condition at power cut and fail safe supply is installed.
1: Close valve
2: Open Valve
3: Maintain valve position
4: Go to OD given by ¡12"
Fail safe supply ¡08 0 1 0
Yes
Fail safe supply connected and enable of A4 alarm:
0: No
1: Yes
DI function ¡09 1 2 1
No
Define function when DI is ON (short circuited DI terminals) when ¡02 = 2
1: Open ICM valve (DI = OFF = > Close ICM valve)
2: Close ICM valve (DI = OFF = > Open ICM valve)
Password ¡10 0 199 0 - -
Enter number to access password protected parameters: ¡26
Password = 11
Old Alarms ¡11 A1 A99 - - No
Old alarms will be listed with the latest shown first. Alarm list can be reset by means
of activating down arrow and up arrow at the same time for 2 seconds.
OD at power cut. ¡12 0 100 50
No
Only active if ¡07 = 4
If fail safe supply is connected and power cut occurs, the valve will go to the specified OD.
Inverse operation ¡13 0 1 0
No
When ¡02 = 1
0: Increasing Analog Input signal => Increasing ICM Opening Degree
1: Increasing Analog Input signal => Decreasing ICM Opening Degree
When ¡02 = 3
0: DI1 = ON, DI2 = OFF => Increasing valve Opening Degree.
DI1 = OFF, DI2 = ON => Decreasing valve Opening Degree
DI1 = DI2 = OFF => ICAD/ICM maintain current position
DI1 = DI2 = ON => ICAD/ICM maintain current position
1: DI1 = ON, DI2 = OFF => Decreasing ICM Opening Degree
DI1 = OFF, DI2 = ON => Increasing ICM Opening Degree
DI1 = DI2 = OFF => ICAD/ICM maintain current position
DI1 = DI2 = ON => ICAD/ICM maintain current position
The first parameter to be entered shall be: ¡26
to be continued....
ENGLISH

Other manuals for Danfoss ICAD 600A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICAD 600A and is the answer not in the manual?

Danfoss ICAD 600A Specifications

General IconGeneral
BrandDanfoss
ModelICAD 600A
CategoryController
LanguageEnglish

Related product manuals