2 Instructions RI8SR1ML © Danfoss 01/2019 AK-PC 572
Connection, lower level Connection, upper level
ENGLISH
Electric noise
Signal cables for sensors, DI inputs, data communication
and display must be kept separate from high voltage
(230 V) electric cables:
- Use separate cable trays
- Keep a distance between high voltage and signal cables
of at least 10 cm
- Cables longer than 3 m at the DI input should be avoided
Connections
DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 Σ 1-8
I Max. 10 A
(3.5)
10 A
(3.5)
6 A
(4)
6 A
(4)
0.5 A
min. 50 mA
Ioff < 1,5 mA
0.5 A
min. 50 mA
Ioff < 1.5 mA
6 A
(4)
6 A
(4)
32 A
U All 24 V or all 230 V a.c.
Warning
The supply voltage
of AI may not share
the signal with
other controllers.
Separate
supply
Warning!
+ must be connected to +
(L to1to 1)
Important!
Wait before connecting the power supply to the
modules!
In order to set the addresses 96 and 97, you must fol-
low the recommended procedure. See page 4.