Installation Instructions
GB
Option 38 - Relay state on low battery detect
(battery products only)
This establishes the position that the relay is driven
to when the unit shuts down due to low battery
state. Press + until Option 38 is displayed, use
V and
Λ to select required setting.
Setting 0 Relay parked with output OFF (factory setting)
Setting 1 Relay parked with output ON
Option 37 - Set time duration of override rule
(Option 36 set to 1 or 2)
This establishes the duration of a temperature
override available to the user. Press + until Option
37 is displayed, use V and Λ to select required
setting.
Setting 0 Next event (factory setting)
Setting 1 1 hour
Setting 2 2 hours
Setting 3 3 hours
Setting 4 4 hours
Option 40 - Number of Events per Day
This sets the thermostat to operate with either 2,
4 or 6 switching events per day or to run it in stat
mode. Press + until option 40 is displayed, use Λ or
V to select required setting.
1 Stat mode
2 Two switching events per day
4 Four switching events per day
6 Six switching events per day (Factory setting)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss TP5001 series and is the answer not in the manual?

Danfoss TP5001 series Specifications

General IconGeneral
DisplayLCD
Power Supply230V AC
MountingWall-mounted
Protection ClassIP30
Ambient Temperature0°C to 45°C
TypeElectronic Room Thermostat
Temperature Range5°C to 30°C
Programming5/2 day programming
Control ModeOn/Off
Switching Current3 A (resistive)
Accuracy±0.5°C