Programming
016 LCP REVERSING
Value:
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reversing function can be
enabled/disabled on the control panel.
NB!:
Local reversing is inactive when operating
in crane profile.
Description of choice:
If Disable [0] is selected in this parameter, the
[FWD/REV] key will be inactive.
017 LCP RESET
Value:
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be
selected/removed from the keyboard.
This key can be used when parameter 002 has been
set for Remote control [0] or Local control [1].
Description of choice:
If Disable [0] is selected in this parameter, the
[RESET] key will be inactive. However, this is not
possible when operating in crane profile.
NB!:
When running in FC profile, do not select
Disable [0] unless an external reset signal has
been connected via the digital inputs.
018 DATA CHANGE LOCK
Value:
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, it is possible to lock the controls
to disable data changes via the control keys.
Description of choice:
If Locked [1] is selected, data changes in the
parameters cannot be made; however, it will
still be possible to make data changes via serial
communication. Parameter 009-012 Display readout
can be changed via the control panel.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.N4.02 - VLT is a registered Danfoss trademark