Page #34 background imageLoading...
Page #34 background image
VLT
®
6000 HVAC Series
Technical data, mains supply 3 x 525-600 V
According to international requirements 6016 6022 6027 6032 6042 6052 6062 6072
Output current I
VLT,N
[A] (550 V) 18 23 28 34 43 54 65 81
I
VLT, MAX
(60 s) [A] (550V) 20 25 31 37 47 59 72 89
I
VLT,N
[A](575V) 17 22 27 3241 526277
I
VLT, MAX
(60 s) [A] (575 V) 19 24 30 35 45 57 68 85
Output S
VLT,N
[kVA] (550 V) 17 22 27 32 41 51 62 77
S
VLT,N
[kVA] (575 V) 17 22 27 32 41 52 62 77
Typical shaft output P
VLT,N
[kW] 11 15 18.5 22 30 37 45 55
Typical shaft output P
VLT,N
[HP] 15 20 25 30 40 50 60 75
Max. copper cable
cross-section to motor
and loadsharing
4)
[mm
2
] 16 16 16 3535 505050
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Min. cable
cross-section to motor
and loadsharing
3)
[mm
2
] 0.5 0.5 0.5 10 10 16 16 16
[AWG]
2)
20 20 20 8 8 6 6 6
Rated Input Current
I
VLT.N
[A] (550 V) 18 22 27 33 42 53 63 79
I
VLT.N
[A] (600 V) 16 21 25 30 38 49 38 72
[mm2] 16 16 16 3535 505050Max copper cable
cross section, power
4)
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Max. prefuses (mains)
1)
[-]/UL [A] 20 30 35 45 60 75 90 100
Efficiency 0.96
Weight IP20 / NEMA 1
[kg]
[Ibs]
23
51
23
51
23
51
30
66
30
66
48
106
48
106
48
106
Estimated power loss at max. load (550 V) [W] 451 576 702 852 1077 1353 1628 2029
Estimated power loss at max. load (600 V) [W] 446 576 707 838 1074 1362 1624 2016
Enclosure
NEMA 1
1. For type of fuse, see section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted
into
the terminals to comply with IP20.
Always comply with national and local regulations on min. cable cross-section.
4. Aluminium cables with cross-section above 35 mm
2
must be connected by use of
an Al-Cu connector.
MG.61.A5.02 - VLT is a registered Danfoss trademark
34

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals