VLT
®
6000 HVAC Series
Mains supply 3 x 525-600 V
According to international requirements VLT type 6152 6172 6222 6272 6352 6402
Output current I
VLT,N
[A] (525-550 V) 162 201 253 303 360 418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178 221 278 333 396 460
I
VLT,N
[A] (551-600 V) 155 192 242 290 344 400
I
VLT, MAX
(60 s) [A]
(551-600 V)
171 211 266 319 378 440
Output S
VLT,N
[kVA] (550 V) 154 191 241 289 343 398
S
VLT,N
[kVA] (575 V) 154 191 241 289 343 398
Typical shaft output [kW] (550 V) 110 132 160 200 250 315
[HP] (575 V) 150 200 250 300 350 400
Max. cable cross-section
to motor
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Max. cable cross-section
to loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Rated input current I
L,N
[A] (550 V) 158 198 245 299 355 408
I
L,N
[A] (575 V) 151 189 234 286 339 390
I
L,N
[A] (690 V) 155 197 240 296 352 400
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Min. cable cross-section to
motor and power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to
brake and loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains)
[-]/UL
[A]
1
315 350 350 400 500 550
Efficiency
3
0,98
Power loss [W] 2963 3430 4051 4867 5493 5852
Weight IP 00 [kg] 82 91 112 123 138 151
Weight IP 21/Nema1 [kg] 96 104 125 136 151 165
Weight IP 54/Nema12 [kg] 96 104 125 136 151 165
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on
the terminals. Min. cable cross-section is the minimum allowed cross-section. Always comply
with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.61.A5.02 - VLT is a registered Danfoss trademark
36

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals