VLT
®
6000 HVAC Series
■ Mains supply 3 x 525-600 V
According to international requirements VLT type 6152 6172 6222 6272 6352 6402
Output current I
VLT,N
[A] (525-550 V) 162 201 253 303 360 418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178 221 278 333 396 460
I
VLT,N
[A] (551-600 V) 155 192 242 290 344 400
I
VLT, MAX
(60 s) [A]
(551-600 V)
171 211 266 319 378 440
Output S
VLT,N
[kVA] (550 V) 154 191 241 289 343 398
S
VLT,N
[kVA] (575 V) 154 191 241 289 343 398
Typical shaft output [kW] (550 V) 110 132 160 200 250 315
[HP] (575 V) 150 200 250 300 350 400
Max. cable cross-section
to motor
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Max. cable cross-section
to loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Rated input current I
L,N
[A] (550 V) 158 198 245 299 355 408
I
L,N
[A] (575 V) 151 189 234 286 339 390
I
L,N
[A] (690 V) 155 197 240 296 352 400
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
2 x 185
2 x 350 mcm
Min. cable cross-section to
motor and power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to
brake and loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains)
[-]/UL
[A]
1
315 350 350 400 500 550
Efficiency
3
0,98
Power loss [W] 2963 3430 4051 4867 5493 5852
Weight IP 00 [kg] 82 91 112 123 138 151
Weight IP 21/Nema1 [kg] 96 104 125 136 151 165
Weight IP 54/Nema12 [kg] 96 104 125 136 151 165
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on
the terminals. Min. cable cross-section is the minimum allowed cross-section. Always comply
with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.61.A5.02 - VLT is a registered Danfoss trademark
36