VLT
®
8000 AQUA
Installation
■ Technical data, mains supply 3 x 525 - 690 V
According to international requirements VLT type 8052 8062 8072 8102 8122
Output current I
VLT,N
[A] (525-550 V) 56 76 90 113 137
I
VLT, MAX
(60 s) [A] (525-550 V) 62 84 99 124 151
I
VLT,N
[A] (551-690 V) 54 73 86 108 131
I
VLT, MAX
(60 s) [A] (551-690 V) 59 80 95 119 144
Output S
VLT,N
[kVA] (550 V) 53 72 86 108 131
S
VLT,N
[kVA] (575 V) 54 73 86 108 130
S
VLT,N
[kVA] (690 V) 65 87 103 129 157
Typical shaft output [kW] (550 V) 37 45 55 75 90
[HP] (575 V) 50 60 75 100 125
[kW] (690 V) 45 55 75 90 110
Max. cable cross-section to
motor
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
Max. cable cross-section to
loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
Rated input current I
L,N
[A] (550 V) 60 77 89 110 130
I
L,N
[A] (575 V) 58 74 85 106 124
I
L,N
[A] (690 V) 58 77 87 109 128
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2x70
2x2/0
Min. cable cross-section to
motor and power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to
brake and loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains) [-]/UL [A]
1
125 160 200 200 250
Efficiency
3
0.97 0.97 0.98 0.98 0.98
Power loss [W] 1458 1717 1913 2262 2662
Weight IP 00 [kg] 82
Weight IP 21/Nema1 [kg] 96
Weight IP 54/Nema12 [kg] 96
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on
the terminals. Min. cable cross-section is the minimum allowed cross-section. Always comply
with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.83.A2.02 - VLT is a registered Danfoss trademark