Derating for ambient temperature
The ambient temperature (T
AMB,MAX
) is the maximum
temperature allowed. The average (T
AMB,MAX
) measured
over 24 hours must be at least 5ºC (9°F) lower.
If VLT 8000 AQUA is operated at temperatures
above 45ºC (113°F), a derating of the continuous
output current is necessary.
The current of VLT 8152-8652, 380-4
80 V and
VLT 8052-8402, 525-690 V, is to be derated
1%/Deg C above 40° C to 55° C maximum.
VLT 8502-8652, 525-690 V is to be der
ated
1.5%/° C above 40° C to 55° C maximum.
Derating for air p
ressure
Below 1000m/3300 ft altitude no derating is necessary.
Above 1000m/3300 ft the ambient temperature (T
AMB
)
or max. output current (I
VLT,MAX
) must be derated
in accordance w
ith the diagram below:
1. Derating of output current versus altitude at
T
AMB
= max. 40°C (113°F)
2. Derating of max. T
AMB
versus altitude at
100% output current.
Switching on the input
Switching on the input depends on the mains
voltage in question.
The table states the waiting time between cut-ins.
Mains voltage 380 V 415 V 460 V
Waiting time 48 s 65 s 89 s
MG.83.A2.02 - VLT is a registered Danfoss trademark
187

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 8000 AQUA series and is the answer not in the manual?

Danfoss VLT 8000 AQUA series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 8000 AQUA series
CategoryDC Drives
LanguageEnglish

Related product manuals