22-31 Power Correction Factor
Range: Function:
100
%*
[1 -
400 %]
Make corrections to the calculated power at
parameter 22-30 No-Flow Power.
If No Flow is detected, when it should not be
detected, decrease the setting. However, if No
Flow is not detected, when it should be
detected, increase the setting to above 100%.
22-32 Low Speed [RPM]
Range: Function:
Size
related*
[ 0 - par.
22-36 RPM]
To be used if 0-02 Motor Speed Unit has
been set for RPM (parameter not visible
if Hz selected).
Set used speed for the 50% level.
This function is used for storing values
needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range: Function:
Size
related*
[ 0 - par.
22-37 Hz]
To be used if 0-02 Motor Speed Unit has
been set for Hz (parameter not visible if
RPM selected).
Set used speed for the 50% level.
The function is used for storing values
needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range: Function:
Size
related*
[ 0 -
5.50 kW]
To be used if 0-03 Regional Settings has
been set for International (parameter not
visible if North America selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range: Function:
Size
related*
[ 0 -
7.50 hp]
To be used if 0-03 Regional Settings has
been set for North America (parameter
not visible if International selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range: Function:
Size
related*
[ 0 - par.
4-13 RPM]
To be used if 0-02 Motor Speed Unit has
been set for RPM (parameter not visible
if Hz selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range: Function:
Size
related*
[ 0 - par.
4-14 Hz]
To be used if 0-02 Motor Speed Unit has
been set for Hz (parameter not visible if
RPM selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range: Function:
Size
related*
[ 0 -
5.50 kW]
To be used if 0-03 Regional Settings has
been set for International (parameter not
visible if North America selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-39 High Speed Power [HP]
Range: Function:
Size
related*
[ 0 -
7.50 hp]
To be used if 0-03 Regional Settings has
been set for North America (parameter
not visible if International selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-40 Minimum Run Time
Range: Function:
60 s* [0 - 600 s] Set the desired minimum running time for
the motor after a start command (digital
input or Bus) before entering Sleep Mode.
22-41 Minimum Sleep Time
Range: Function:
30 s* [0 - 600 s] Set the desired Minimum Time for staying in
Sleep Mode. This overrides any wake up
conditions.
22-42 Wake-up Speed [RPM]
Range: Function:
Size
related*
[ 0 -
par.
4-13
RPM]
To be used if 0-02 Motor Speed Unit has
been set for RPM (parameter not visible if
Hz selected). Only to be used if
parameter 1-00 Configuration Mode is set for
open loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep
Mode should be cancelled.
How to programme the freque...