What to do if Danfoss VLT AutomationDrive FC 361 DC Drives show DC overvoltage?
- RRebecca RobinsonAug 19, 2025
If the DC-link voltage exceeds the limit, the drive trips after a certain time. To resolve this, connect a brake resistor, extend the ramp time, change the ramp type, activate the functions in parameter 2-10 Brake Function, or increase parameter 14-26 Trip Delay at Inverter Fault.