What to do if my Danfoss VLT AutomationDrive FC 303 DC Drives display is dark?
- AAmanda NelsonAug 17, 2025
If the Danfoss DC Drives display is dark, it could be due to several reasons. First, check the input power source. Also, check for missing or open fuses, or a tripped circuit breaker. Ensure there is power to the LCP and that there isn't a short circuit on the control voltage terminals. Verify you are using the correct LCP model (LCP 101 or LCP 102). Adjust the contrast by pressing [Status] + Up/Down arrows. If none of these steps work, the display (LCP) or the internal voltage supply might be defective.